Description
The CTS-2000 family of split-core CTs have a removable section, so that they can be installed without interrupting the circuit
- They have a rectangular window opening of 2″ x 2″ and are available in five rated current ranges from 400A to 1200A
- Safe: burden resistor built-in, 0.333 Vac (333 mVac) voltage output at rated full scale current, no shorting blocks needed!
- Accuracy ±1% from 10% to 100% of rated current
- Line frequency: 50-60 Hz
- Phase angle <2° degrees at 50% of rated current
- Lead wires 8 ft. long, #22 AWG 600 Vac rated, black and white, twisted-pair
- UL recognized for voltages up to 600 Vac, CE mark, RoHS
- No exposed metal
- Qualified under the Buy American provision in the American Recovery and Reinvestment Act of 2009 (ARRA)
| Part No (Socomec) |
Old Part No (CCS) |
Input Rating (A) |
| 4873420C |
CTS-2000-0400 |
400 |
| 4873420D |
CTS-2000-0600 |
600 |
| 4873420E |
CTS-2000-0800 |
800 |
| 4873420F Discontinued. Replace with SCT-2000-1000 |
CTS-2000-1000 |
1000 |
| 4873420G Discontinued. Replace with SCT-2000-1200 |
CTS-2000-1200 |
1200 |